10 KVA to 500 KVA
ETL Listed to UL1778 and UL924
Incandescent, Fluorescent, HID, HPS, LED
Power Factor & Energy Efficient Ballast
Sinusoidal Waveform
Pulse Width Modulated (PWM)
Generator Compatible
LCD Panel for Continuous Self Diagnostics
Modular Assembly for Ease of Installation
Intelligent Battery Test
Double Conversion Technology
Seismic Rated with Bracket Kit
Remote Monitoring
RS-232 and RS-485
Optional Global Monitoring System (GMS)
Optional Battery Monitoring System (BMS)
2 Year Factory Warranty
Power Rating | 10, 20, 30, 40,50, 60, 80, 100, 120, and 160 KVA, 0.8PF 200, 240, 300, 400, and 500 KVA are also available upon request |
Input Voltage | 208Y/120 or 480Y/277 VAC (-15% to +15%) |
Output Voltages | 208Y/120 or 480Y/277 VAC |
Output Frequency (Inverter Operation) |
60 Hz ±0.1 Hz |
Voltage Regulation | ±1% at 100% unbalanced load |
Output Wave Form | Sine-Wave < 2% THD. |
Crest Factor | 3:1 Typical |
Surge Protection | The UPS will protect itself and the load against surges as defined in ANSI/IEEE C62.41 Categories A and B. |
Isolation | True galvanic isolated |
Noise Isolation | -120 dB Common-Mode; -60 dB Transverse-Mode |
Battery | Sealed maintenance-free VRLA or long life battery |
Recharge Current | Varies per KVA and conforms to UL924 |
Humidity | 0 - 95% RH w/ no condensation |
Operating Temperature | UPS: 0° to 40°C. (32° - 104°F) Battery: 20° to 30°C. (68° - 86°F) Higher temperature batteries are available for special order |
Storage Temperature | -20° to 60°C. (-4° - 140°F) |
Altitude | Up to 10,000 ft |
Safety Agencies | CUL, CSA Listed UL1778, UL924 |
Cabinet Size (UPS Only) |
10-60kVA: 34" Wide x 31.5" Deep x 63" High 80-160kVA: 55.5" Wide x 31.5" Deep x 63" High 200-320kVA: 86.5" Wide x 31.5" Deep x 63" High 400kVA: 133" Wide x 39.5" Deep x 71" High 500kVA: 178" Wide x 39.5" Deep x 71" High |
Battery Cabinet Size | 51" Wide x 30.5" Deep x 70" High |
Emergency Lighting: Production Facility, Testing Lab, Telecommunications, Industrial, Government, Public Building, School, Cruise Line, Banking, Hospitals, Printing Facility.
All type of lighting including self-ballast Fluorescent, Incandescent, Quartz re-strike, Halogen, HID, HPS and LED lighting.