| Sizes |
15 to 1,250 kVA
|
| Input Voltage* |
208 or 480 VAC |
| Output Voltage* |
208Y/120 or 480Y/277 VAC
|
| Frequency* |
50 or 60 Hz, ±5% |
| Response Time |
1 cycle typical |
| Harmonic Distortion |
1% max. added at switching
|
| Audible Noise |
Meets or exceeds NEMA standards
|
| Common-Mode |
-120 dB <300 kVA |
| Normal-Mode |
-60 dB/decade |
| Neutral to Ground |
0.5V max. potential
|
| Overload (Inrush) |
200% of full load for 10 second 1000% of full load for 1cycle
|
Input Voltage
Regulation Range |
+8% to -10% of nominal
|
Output Voltage |
| Regulation Range |
±1.5% typical, ±2% maximum phase imbalance
|
| Voltage Surges |
20% max. above nominal voltage, 50 milliseconds max. duration
|
| Voltage Sags |
30% max. below nominal voltage, 20 milliseconds max. duration
|
| Line Transients |
20% above nominal voltage 1/hr. max.
|
| Efficiency |
>96% at 80% of load |
| Load Power Factor |
0.3 leading or lagging to unity
|
| Transformer Type |
|
| <300 kVA |
3 phase computer grade, dual-shielded, copper wounded, isolation transformer |
| >400 kVA |
3 phase, copper wound, buck-boost transformer |
| Transformer Impedance |
3 to 5% (low impedance) |
Environmental |
| Operating Temperature |
32°(0°C) to 104°F (40°C)
|
| Operating Humidity |
10 to 90% non-condensing
|
| Operating Temperature |
32°F (0°C) to 104°F (40°C)
|
| Storage Temperature |
-4°F (-20°C) to 140°F (60°C)
|
| Operating Humidity |
5 to 95% non-condensing |
|
* Other voltages and frequencies available.
|