Input |
| Voltage (Nominal) |
480 VAC, 3ø, 3W + Gnd
|
| Voltage Range |
+20%, -20% (without batteries) |
| Frequency |
50/60 Hz ±5Hz
|
| Protection |
Auto & Maintenance Bypass |
Output |
| Power Rating |
10, 15, 20, 25, 30, 40, 50, 60, 80, 100, 120, 160, 200 kVA (consult factory for other sizes)
|
| Power Factor Rating |
0.8
|
| Voltage |
480 VAC, 3 Phase, 4 Wires + Gnd
|
| Crest Fator |
3:1
|
| Voltage Regulation |
±1% |
| Dynamic Regulation |
±2% for Step Load
|
| Phase Imbalance |
V thd <2%
|
| Frequency Stability |
±1% |
| Overload Rating |
150% for 30 Seconds,
125% for 15 minutes |
| Neutral |
Newly derived and bonded to earth |
Physical |
| Cabinet Dimensions |
44"W x 31.5”D x 63”H (w/Batteries) |
| Electrical Connection |
Front Access |
| Cable Entry/Exit |
Bottom |
| Service Clearance |
Modular design for ease of service (Front Only) |
| Operating Temperature |
32°(0°C) to 10c°F (40°C) (control cabinet),
25˚C (77˚F) (battery cabinet)
|
| Operating Humidity |
10 to 90% non-condensing
|
| Seismic Anchoring |
Mounting Brackets (optional)
|
System |
| Configuration |
Three Phase UPS modular design for easy of service |
| Topology |
Advanced Double Conversion |
| Technology |
Redundant DSP, microprocessor |
| Efficiency |
92% typical |
| Bypass 1 |
Static Reverse |
| Bypass 2 |
Internal Maintenance |
| Audible Noise |
<67 dBA at 1 Meter |
| Cooling |
Intelligent speed controlled Forced Air |
| Heat Dissipation |
6600 BTU Typical |
Communication |
| Interface |
RS485, RS232, Relay Contacts |
| Display |
Front Mimic Panel LCD (4 lines X 40 Character backlit LCD) |
| Audible Alarm |
Yes / Programmable |
| Emergency Shut Down |
Local & remote Capability (optional) |
| Network Capable |
Yes (optional) |
Global Monitoring System (Option)
LOCAL: Local PC via RS232 and RS485
REMOTE: Web/SNMP and Dial-up |
|
Due to continuous improvement, specifications are subject to change without prior notification.
|