| Sizes |
1, 1.5, 2, 2.5 and 3 kVA (Single Phase)
|
| Input Voltage* |
120 or 208 or 240 VAC
|
| Output Voltage* |
120 or 120/240 VAC
|
| Frequency* |
50 Hz or 60 Hz +5%
|
| Response Time |
1 cycle typical
|
| Harmonic Distortion |
<1% maximum added
|
| Audible Noise |
Meets or exceeds NEMA standards
|
| Common-Mode |
-120 dB (.1 Hz to 10
MHz)
|
| Normal-Mode |
-60 dB/decade (1KHz to 10 MHz)
|
| Overload (Inrush) |
200% of full load for 10 seconds 1000% of full load for
1 cycle |
| Load Rating |
Continuous, regardless of load/line conditions
|
Voltage Regulation
Range Input
|
+7% to -23% of nominal |
| Output |
+5% typ. +6% All line-load conditions
|
| Efficiency |
96% min.
|
| CP3 Output Receptacle |
2 optional receptacle positions
|
| Load Power Factor |
0.3 leading or lagging to unity |
| Transformer |
Single phase, dual-shielded, computer grade, iso-lation
transformer, copper wound |
Environmental |
| Operating Temperature |
32°F (0°C) to 104°F (40°C)
|
| Storage Temperature |
-4°F (-20°C) to 140°F (60°C)
|
| Operating Humidity |
10 to 95% non-condensing
|
Dimension
|
|
Constant Power 3
|
10.5" (27 cm) high
|
|
11" (28 cm) wide
|
|
16" (41 cm) deep
|
|
Mini Power
|
12" (30 cm) high |
|
6.5" (17 cm) wide |
|
12" (30 cm) deep |
* Other voltages and frequencies available. |