+ 1 to 3 KVA
+ Ready to "Plug and Play"
+ Solid State and Economical
+ EMI Shielded, High Isolation
+ Heavy-duty Filters
+ Voltage Regulation
+ Output Distribution
+ 1 Year Factory Warranty
Sizes | 1, 1.5, 2, 2.5 and 3 KVA (Single Phase) |
Input Voltage | 120 or 208 or 240 VAC |
Output Voltage | 120 or 120/240 VAC |
Frequency | 50 Hz or 60 Hz ±5% |
Response Time | 1 cycle typical |
Harmonic Distortion | <1% maximum added |
Audible Noise | Meets or exceeds NEMA standards |
Common-Mode | -120 dB (.1 Hz to 10 MHz) |
Normal-Mode | -60 dB/decade (1KHz to 10 MHz) |
Overload (Inrush) | 200% of full load for 10 seconds 1000% of full load for 1 cycle |
Load Rating | Continuous, regardless of load/line conditions |
Input Volt Regulation Range |
+7% to -23% of nominal |
Output Volt Regulation Range | ±5% typ. ±6% All line-load conditions |
Efficiency | 96% min. |
CP3 Output Receptacle | 2 optional receptacle positions |
Load Power Factor | 0.3 leading or lagging to unity |
Transformer | Single phase, dual-shielded, computer grade, iso-lation transformer, copper wound |
Operating Temperature | 32°F (0°C) to 104°F (40°C) |
Storage Temperature | -4°F (-20°C) to 140°F (60°C) |
Operating Humidity | 10 to 95% non-condensing |
Mini Power |
12"H x 6.5"W x 12"D |
Constant Power 3 |
10.5"H x 11"W x 16"D |
Computer Room • Production Facility • Testing Lab • Telecommunications Retail Sales / POS • Industrial • Government • Public Building • Schools Library • Healthcare • Cruise Line • Banking / Credit • Printing Facility