Power-Reg & Ultra-Reg

Product Details
Specification
Data Sheets
Technical Drawings
User manual

Features

±3% Output Voltage Regulation
Input Filter (-40 dB)
Power-Reg: (<300 kVA) -120 dB
   Common-mode
Ultra-Reg: (<300 kVA) -126 dB
   Common-mode
High Efficiency
Low Distortion
Single Point Grounding
Zero Current Tap Switching
Excellent Voltage Regulation
2 year Factory Warranty


Specifications

  Sizes 15, 30, 50, 75, 100, 125, 150,175, 200, 225, 250, 300, 400,500, 625, 750, 875, 1000, and 1250
  Input Voltage* 208 or 480 VAC, **480Y/277
  Output Voltage* 208Y/120 or 480Y/277 VAC
  Frequency* 60 Hz ±5%
  Response Time 1 cycle typical
  Harmonic Distortion 1% Max. Added at Switching
Voltage Regulation Range
  Input +10% to -26% of nominal
  Output ±3% typ. ±4% maximum
  Common-Mode -120 dB. (<300 kVA) -140 dB -146 dB or -156 dB available
  Normal-Mode 40 dB/decade
  Overload(Inrush) 200% of full load for 10 seconds; 1000% of full load for 1 cycle
Transformer
<300 kVA
3 phase computer grade, dual-shielded, isolation transformer
>400 kVA
3 phase, copper wound, buck-boost transformer
  Efficiency 96% at full loads; 98.5% at light loads
  Load Power Factor 0.3 leading or lagging to unity
  Audible Noise Meets or exceeds NEMA stan-dards

Environmental
  Operating Temp 32°F.(0°C.) to 104°F.(40°C.)
  Storage Temp -4°F.(-20°C.) to 140°F.(60°C.)
  Operating Humidity 10 to 90% non-condensing
  Transformer Impedance 3 to 5%
* Other voltages and frequencies available.



       Copyright © 2002 Onlinepower, Inc. All rights reserved.