Features |
|
15 to 450 kVA
UL Listed
High Efficiency(>96%)
Tight Output Voltage Regulation (±3%)
High Isolation
Built-In Distribution
Overload Protection
Output Conduit Landing Bracket
Remote Distribution Capability
Easy to Install
2 Year Factory Warranty |
|
|
|
|
Specifications
|
|
|
| Sizes |
15, 30, 50, 75,100,125, 175, 200, 225, 250, 300, 350, 400, and 450 kVA
|
| Input Voltage* |
208 or 480 VAC
|
| Output Voltage* |
208 Y/120 VAC
|
| Frequency* |
60 Hz ±5%
|
| Response Time |
1 cycle typical
|
| Harmonic Distortion |
1% max. added
|
| Audible Noise |
Meets or exceeds NEMA stan-dard
|
| Common-Mode |
-120 dB
|
| Normal-Mode |
-40 dB/decade
|
| Overload (Inrush) |
200% of full load for 10 seconds 1000% of full load for 1 cycle
|
Voltage Regulation |
| Input |
+10% to -26% of nominal |
| Output |
±3% typ. cycle |
| Efficiency |
>96% |
| Load Power Factor |
0.3 leading or lagging to unity |
| Transformer |
3 phase computer grade dual-shielded, isolation transformer
|
| Transformer Impedance |
3 to 5% |
| Cooling |
Convection |
Environmental |
| Operating Temp |
32°F.(0°C.) to 104°F.(40°C.)
|
| Operating Humidity |
10 to 90% non-condensing
|
| Transformer Impedance |
3 to 5%
|
Dimension |
| Main Unit |
73"(H)X34"(W)X35.5"(D)
|
| Side Car |
73"(H)X34"(W)X12"(D)
|
|
* Other voltages and frequencies available.
|
|
|
|
 |
|
|
|
|
 |