Industrial Grade 3000

Product Details
Specification
Data Sheets
Technical Drawings
User manual

Features

15 to 100KVA
UL 924 (Optional)
High Reliability & High Efficiency
Acoustically Quiet
Ease of Installation
Full Double Conversion
Fully Rated Static Switch
Maintenance Bypass Switch
Transistorized Inverter Suitable for 100% Non-Linear
   Loads with 3.5 Crest Factor
5 Year Factory Warranty



Specifications

 INPUT
  Voltage 208Y/120, 480Y/277 VAC
  Voltage Range +10%, -15%
  Wiring 3 Phase, 3 Wire and Ground
  Power Factor 0.85
  Frequency Range 60 Hz. ±5%
  Magnetizing In Rush 5-8 times normal Full Load cur-rent
  Power Walk-In 20 to 100% in 15 Sec.
  Current Limit 00-125% of normal Full Load current adjustable
  Protection Molded case circuit breaker with single phase protection. Currentlimit fuses.
OUTPUT
  Voltage 60 Hz 208Y/120 or 480Y/277 VAC
  Wiring 3 Phase, 4 Wire and Ground
 Voltage Regulation

  Balanced Load +0.5%
  50% Unbalanced +2%
  100% Unbalanced +5%
  Frequency(Regulation) +0.1%
  Efficiency 92%
  Load Power Factor 0.7 Lag to 0.9 Lead
  Phasing Balance

    Balanced Load 120° ±1°
    50% Unbalanced 120° ±1°
    100% Unbalanced 120° ±3°
  Total Harmonics 3% RMS Max
  Single Harmonics 1% RMS Max.
  Overload at 125% of Full Load for 10Minutes.
  Nominal 150% of Full Load for 30 sec-onds.
  Current Limit 150% FL current at reduced volt-age
  Fault Clearing Capability 300-400% sub-cycle
  Voltage Transients
    50% Load step +3%
   100% Load step +5%
    Loss or return of
  
  redundant  module
+3%
   Automatic transfer +3% Load to Bypass
   Manual Return +1% Load to UPS
   Response Time Recovery to 99% of steady state in 1 cycle.
ENVIROMENT
  Operating Temp UPS:  0° to 40° C. (32° to 104° F)
BATTERY:  20
° to 30° (68° to 86° F)
  Non - Operating Temp -20 to 70 C. (-4 to 158 F)
  Battery Temp Average annual temperature less than 27C. (80F). Peak temperature less than 43C. (110F.) fro more than 24- hour period.
  Relative Humidity 5-95% Non-condensing
  Altitude
     Operating Up to 7,500 ft. (2,286 m)
     Non-operating Up to 10,000 ft. (3,048 m)
     Acoustical Noise <45 db at 6 ft.
  Dimensions 34"(W) X 34"(D) X 69"(H)
  
kVA
sizes
Input
Voltage
Output
Voltage
Model
Numbers
BTU's/HR
UPS
Weight
Battery Cabinet Weight
15 Min
30 Min
45 Min
15
208 VAC
208 VAC UP015B0500T3
4,440
1,655 LBS
1,243
1,495
2,900
408 VAC 408 VAC UP015H0900T3
20
208 VAC 208 VAC UP020B0500T3
5,900
1,998 LBS
1,618
2,050
3,270
408 VAC 408 VAC UP020H0900T3
25
208 VAC 208 VAC UP025B0500T3
7,400
2,092 LBS
1,800
2,144
3,900
408 VAC 408 VAC UP025H0900T3
30
208 VAC 208 VAC UP030B0500T3
8,900
2,186 LBS
2,144
2,800
4,100
408 VAC 408 VAC UP030H0900T3
37.5
208 VAC 208 VAC UP037B0500T3
11,100
2,331 LBS
2,144
2,800
4,900*
408 VAC 408 VAC UP037H0500T3
50
208 VAC 208 VAC UP050B0500T3
15,000
2,566 LBS
2,800
4,940*
5,600*
408 VAC 408 VAC UP050H0900T3
62.5
208 VAC 208 VAC UP062H0500T3
Consult Factory
408 VAC 408 VAC UP062H0900T3
75
208 VAC 208 VAC UP075H0500T3
408 VAC 408 VAC UP075H0900T3
100
208 VAC 208 VAC UP100H0500T3
408 VAC 408 VAC UP100H0900T3
* Two(2) Battery Cabinets.