Industrial Grade 3000
|
|
|
Product Details
|
|
|
Specification
|
 |
Data Sheets
|
 |
Technical Drawings
|
 |
User manual |
|
|
|
|
|
|
 |
|
Features |
|
15 to 100KVA
UL 924 (Optional)
High Reliability & High Efficiency
Acoustically Quiet
Ease of Installation
Full Double Conversion
Fully Rated Static Switch
Maintenance Bypass Switch
Transistorized Inverter Suitable for 100% Non-Linear
Loads with 3.5 Crest Factor
5 Year Factory Warranty
|
|
|
|
|
Specifications
|
|
|
| INPUT |
| Voltage |
208Y/120, 480Y/277 VAC
|
| Voltage Range |
+10%, -15%
|
| Wiring |
3 Phase, 3 Wire and Ground
|
| Power Factor |
0.85
|
| Frequency Range |
60 Hz. ±5%
|
| Magnetizing In Rush |
5-8 times normal Full Load cur-rent |
| Power Walk-In |
20 to 100% in 15 Sec. |
| Current Limit |
00-125% of normal Full Load current adjustable |
| Protection |
Molded case circuit breaker with single phase protection. Currentlimit fuses.
|
OUTPUT
|
| Voltage 60 Hz |
208Y/120 or 480Y/277 VAC
|
| Wiring |
3 Phase, 4 Wire and Ground
|
Voltage Regulation
|
|
| Balanced Load |
+0.5%
|
| 50% Unbalanced |
+2%
|
| 100% Unbalanced |
+5%
|
| Frequency(Regulation) |
+0.1%
|
| Efficiency |
92% |
| Load Power Factor |
0.7 Lag to 0.9 Lead |
Phasing Balance
|
|
| Balanced Load |
120° ±1° |
| 50% Unbalanced |
120° ±1° |
| 100% Unbalanced |
120° ±3° |
| Total Harmonics |
3% RMS Max |
| Single Harmonics |
1% RMS Max. |
| Overload at |
125% of Full Load for 10Minutes. |
| Nominal |
150% of Full Load for 30 sec-onds.
|
| Current Limit |
150% FL current at reduced volt-age |
| Fault Clearing Capability |
300-400% sub-cycle
|
| Voltage Transients |
|
| 50% Load step |
+3%
|
| 100% Load step |
+5%
|
Loss or return of
redundant module |
+3%
|
| Automatic transfer |
+3% Load to Bypass
|
| Manual Return |
+1% Load to UPS
|
| Response Time |
Recovery to 99% of steady state in 1 cycle. |
ENVIROMENT
|
| Operating Temp |
UPS:
0° to 40°
C. (32° to
104° F)
BATTERY: 20°
to 30°
(68°
to 86°
F) |
| Non - Operating Temp |
-20 to 70 C. (-4 to 158 F) |
| Battery Temp |
Average annual temperature less than 27C. (80F). Peak temperature less than 43C. (110F.) fro more than 24- hour period. |
| Relative Humidity |
5-95% Non-condensing |
| Altitude |
|
| Operating |
Up to 7,500 ft. (2,286 m) |
| Non-operating |
Up to 10,000 ft. (3,048 m) |
| Acoustical Noise |
<45 db at 6 ft. |
| Dimensions |
34"(W) X 34"(D) X 69"(H) |
kVA
sizes
|
Input
Voltage
|
Output
Voltage
|
Model
Numbers
|
BTU's/HR
|
UPS
Weight
|
Battery Cabinet Weight
|
|
15 Min
|
30 Min
|
45 Min
|
|
15
|
208 VAC
|
208 VAC |
UP015B0500T3 |
4,440
|
1,655 LBS
|
1,243
|
1,495
|
2,900
|
| 408 VAC |
408 VAC |
UP015H0900T3 |
|
20
|
208 VAC |
208 VAC |
UP020B0500T3 |
5,900
|
1,998 LBS
|
1,618
|
2,050
|
3,270
|
| 408 VAC |
408 VAC |
UP020H0900T3 |
|
25
|
208 VAC |
208 VAC |
UP025B0500T3 |
7,400
|
2,092 LBS
|
1,800
|
2,144
|
3,900
|
| 408 VAC |
408 VAC |
UP025H0900T3 |
|
30
|
208 VAC |
208 VAC |
UP030B0500T3 |
8,900
|
2,186 LBS
|
2,144
|
2,800
|
4,100
|
| 408 VAC |
408 VAC |
UP030H0900T3 |
|
37.5
|
208 VAC |
208 VAC |
UP037B0500T3 |
11,100
|
2,331 LBS
|
2,144
|
2,800
|
4,900*
|
| 408 VAC |
408 VAC |
UP037H0500T3 |
|
50
|
208 VAC |
208 VAC |
UP050B0500T3 |
15,000
|
2,566 LBS
|
2,800
|
4,940*
|
5,600*
|
| 408 VAC |
408 VAC |
UP050H0900T3 |
|
62.5
|
208 VAC |
208 VAC |
UP062H0500T3 |
Consult Factory
|
| 408 VAC |
408 VAC |
UP062H0900T3 |
|
75
|
208 VAC |
208 VAC |
UP075H0500T3 |
| 408 VAC |
408 VAC |
UP075H0900T3 |
|
100
|
208 VAC |
208 VAC |
UP100H0500T3 |
| 408 VAC |
408 VAC |
UP100H0900T3 |
|
|
* Two(2) Battery Cabinets.
|
|
|
|
 |
|
|
|
|
 |