| Sizes |
15, 30, 50, 75 and *100 kVA
|
| Input Voltage** |
208 or 480 VAC
|
| Output Voltage** |
208 Y/120 or 480 Y/277 VAC
|
| Frequency* |
60 Hz. ±5%
|
| Response Time |
1 cycle typical
|
| Harmonic Distortion |
1% max. added at tap switching
|
| Audible Noise |
Meets or exceeds NEMA standards
|
| Common-Mode |
-120 dB |
| Normal-Mode |
-40 dB/decade |
| Overload (Inrush) |
200% of full load for 10 seconds 1000% of full load for 1 cycle
|
Input Voltage
|
| Regulation Range |
+10% to -26% of nominal |
Output Voltage |
| Regulation Range |
±3% typ. ±4% maximum
|
| Efficiency |
96% at full load 98.5% at light load
|
| Load Power Factor |
0.3 leading or lagging to unity
|
| Crest Factor |
3:1 maximum
|
| Transformer |
3 phase computer grade, dual-shielded, copper wounded, isolation trans-former
|
| Transformer Impedance |
3 to 5%
|
3 Phase Power On
Indicator |
Neon
|
| Input Voltage Cooling |
Convection
|
Environmental |
| Operating Temperature |
32°F (0°C) to 104°F (40°C)
|
| Storage Temperature |
-4°F (-20°C) to 140°F (60°C)
|
| Operating Humidity |
5 to 95% non-condensing |
Dimensions |
|
15 - 50 kVA
|
42" (107 cm) Height
|
32" (81 cm) Width
|
22" (56 cm) Depth
|
|
75/100 kVA
|
42" (107 cm) Height
|
32" (81 cm) Width
|
27" (69 cm) Depth
|
* 100 kVA only available in 480 volts input
** Other voltages and Frequencies available contact factory.
- Specifications are subject to change without prior notification. - |